NDT Ops

Armstrong International

AIM ST5700 Series (WirelessHART)

Request a quote Source: carotek.com

Source: carotek.com (accessed 2026-10-16). Confirm specifications with the manufacturer before ordering.

Specifications

Vendor
Armstrong International
Brand / line
AIM
Category
Leak, valve and steam
Class
Adjacent
Technique
Steam-trap-specific acoustic plus temperature sensing via patented waveguide
Detects
steam trap failuretemperature
Mounting
Clamp-on at inlet of steam trap, non-intrusive; pipe DN15-DN150 (0.5-6 in)
Temperature range
Ambient -40 to 90 °C; max process 440 °C; min operating pressure 1 barg
Communications
WirelessHART
Power
Tadiran TLH-5920 lithium-metal battery; estimated battery life reported
Suitable assets
steam systemsvalves
Notes
Integrates with Armstrong SAGE software. IP66. Brochure 303-EN (2017) hosted by distributor Carotek; hazardous-area rating not stated in brochure.

Related in Leak, valve and steam