NDT Ops

Emerson

Rosemount 708 Wireless Acoustic Transmitter

Request a quote Source: emerson.com

Source: emerson.com (accessed 2026-10-16). Confirm specifications with the manufacturer before ordering.

Specifications

Vendor
Emerson
Brand / line
Rosemount
Category
Leak, valve and steam
Class
Adjacent
Technique
Ultrasonic acoustic event detection (ultrasonic sensor peak sensitivity 35-45 kHz) plus thermocouple
Detects
steam trap failurevalve passingtemperatureleaks
Mounting
Clamp-on to piping/PRV discharge line with mounting bands, non-intrusive, no process shutdown or hot work
Temperature range
Process surface up to 260 °C (500 °F) per quick start guide; high-temperature mounting hardware above that
Communications
WirelessHART
Power
Replaceable SmartPower lithium-thionyl chloride module, up to 10 years depending on update rate
Hazardous area
FM, CSA, ATEX (Ex ia IIC T4 Ga) and IECEx intrinsically safe
Suitable assets
steam systemsvalvespiping
Notes
Optional Steam Trap Monitor software; connects via Emerson Wireless 1410S Gateway (HART-IP, OPC UA, Modbus, EtherNet/IP). Valve-agnostic for PRVs. Temp/approval detail from Emerson 708 quick start guide (88536).

Related in Leak, valve and steam